The microclimate provided by ventilation systems in a residential or industrial building affects the well-being and performance of people. To create comfortable living conditions, standards have been developed that determine the composition of air. Agree, regular air exchange is vital.
We will tell you what should be the air velocity in the duct. We advise you what to do so that the airflow always remains fresh and meets hygiene standards. Here you will find a detailed description of the calculation methods and a listing of the rules for selecting the optimal duct.
The information proposed for familiarization is based on the data of normative directories. For practical development of calculation methods, examples are given. The text material is supplemented by visual illustrations and videos that facilitate the perception of a difficult topic.
The importance of air exchange for humans
According to construction and hygiene standards, each residential or industrial facility must be provided with a ventilation system.
Its main purpose is to maintain air balance and create a microclimate favorable for work and rest. This means that in the atmosphere that people breathe, there should not be an excess of heat, moisture, pollution of various kinds.
Violations in the organization of the ventilation system lead to the development of infectious diseases and diseases of the respiratory system, to a decrease in immunity, to premature spoilage of food.
In an excessively humid and warm environment, pathogens develop rapidly, foci of mold and fungus appear on walls, ceilings and even on furniture.
The ventilation scheme in a two-story private house. The ventilation system is equipped with a supply and exhaust energy-saving installation with a heat recuperator, which allows you to reuse the heat of the air removed from the building
One of the conditions for maintaining a healthy air balance is the proper design of the ventilation system. Each part of the air exchange network must be selected based on the volume of the room and the characteristics of the air in it.
Suppose that in a small apartment there is a sufficiently well-adjusted supply and exhaust ventilation, while installation of equipment for forced air exchange is mandatory in production shops.
During the construction of houses, public institutions, workshops, enterprises are guided by the following principles:
- each room must be provided with a ventilation system;
- it is necessary to observe the hygienic parameters of the air;
- enterprises should install devices that increase and regulate the rate of air exchange; in residential premises - air conditioners or fans, provided there is insufficient ventilation;
- in premises for various purposes (for example, in wards for patients and the operating room or in the office and in the smoking room), it is necessary to equip different systems.
In order for ventilation to meet the listed conditions, you need to make calculations and choose equipment - air supply devices and air ducts.
Also, when installing a ventilation system, it is necessary to choose the right places for air intake in order to prevent polluted flows from entering the premises.
In the process of drawing up a ventilation project for a private house, a multi-story residential building or industrial premises, the air volume is calculated and the installation sites of ventilation equipment are planned: water exchange plants, air conditioners and air ducts
The efficiency of air exchange depends on the size of the ducts (including house mines). We will find out what are the norms of the air flow rate in ventilation indicated in the sanitary documentation.
Image Gallery
Photo from
Ventilation system in the attic of a house
Supply and exhaust ventilation equipment
Rectangular plastic ducts
Local duct resistance
Rules for determining air velocity
Air speed is closely interconnected with concepts such as noise level and vibration level in the ventilation system. The air passing through the channels creates a certain noise and pressure, which increase with an increase in the number of turns and bends.
The greater the resistance in the pipes, the lower the air speed and the higher the fan performance. Consider the norms of related factors.
No. 1 - sanitary noise standards
The standards specified in SNiP relate to residential premises (private and multi-apartment buildings), public and industrial type.
In the table below, you can compare the norms for different types of rooms, as well as territories adjacent to buildings.
Part of the table from No. 1 SNiP-2-77 from the paragraph "Noise Protection". The maximum allowable norms relating to night time are lower than daytime values, and the norms for adjacent areas are higher than for residential premises
One of the reasons for the increase in the adopted standards may be just the wrongly designed duct system.
Sound pressure levels are presented in another table:
When commissioning ventilation or other equipment associated with the provision of a favorable, healthy microclimate in the room, only a short-term excess of the indicated noise parameters is allowed
No. 2 - vibration level
The power of fans is directly related to the level of vibration.
The maximum vibration threshold depends on several factors:
- duct dimensions;
- the quality of gaskets, providing a decrease in the level of vibration;
- pipe manufacturing material;
- air flow rates passing through the channels.
The standards that should be followed when choosing ventilation devices and when calculating air ducts are presented in the following table:
Maximum permissible local vibration values. If during the check the real values are higher than normal, then the duct system is designed with technical flaws that need to be fixed, or the fan power is too large
The air speed in the mines and channels should not affect the increase in vibration indicators, as well as the related parameters of sound vibrations.
No. 3 - air exchange rate
Air purification is due to the process of air exchange, which is divided into natural or forced.
In the first case, it is carried out when opening doors, transoms, window leaves, windows (and is called aeration) or simply by infiltration through cracks at the joints of walls, doors and windows, in the second - using air conditioners and ventilation equipment.
The change of air in a room, utility room or workshop should occur several times per hour, so that the degree of contamination of the air mass is acceptable. The number of shifts is the multiplicity, the value also necessary to determine the air speed in the ventilation ducts.
The multiplicity is calculated by the following formula:
N = V / W,
Where:
- N - the rate of air exchange, once every 1 hour;
- V - the amount of clean air filling the room for 1 h, m³ / h;
- W - volume of the room, m³.
In order not to perform additional calculations, the average multiplicity indicators are collected in tables.
For example, for residential premises, the following air exchange rate table is suitable:
Judging by the table, a frequent change of air masses in a room is necessary if it is characterized by high humidity or air temperature - for example, in a kitchen or a bathroom. Accordingly, with insufficient natural ventilation, forced circulation devices are installed in these rooms
What will happen if the air exchange rate standards are not respected or are, but not enough?
One of two things will happen:
- The multiplicity is below the norm. Fresh air stops replacing polluted air, as a result of which the concentration of harmful substances in the room increases: bacteria, pathogens, and dangerous gases. The amount of oxygen, which is important for the human respiratory system, decreases, and carbon dioxide, on the contrary, increases. Humidity rises to the maximum, which is fraught with the appearance of mold.
- Multiplicity is higher than normal. It occurs if the air velocity in the channels exceeds the norm. This negatively affects the temperature regime: the room just does not have time to heat up. Excessively dry air provokes diseases of the skin and respiratory apparatus.
To multiply the air exchange in accordance with sanitary standards, it is necessary to install, remove or adjust the ventilation devices, and if necessary, replace the air ducts.
Air Velocity Algorithm
Given the above conditions and technical parameters of a particular room, you can determine the characteristics of the ventilation system, as well as calculate the air velocity in the pipes.
It should be based on the multiplicity of air exchange, which is the determining value for these calculations.
To clarify the flow parameters, a table is useful:
The table shows the dimensions of the ducts with a rectangular cross section, that is, their length and width are indicated. For example, when using 200 mm x 200 mm channels at a speed of 5 m / s, the air flow will be 720 m³ / h
In order to make calculations yourself, you need to know the volume of the room and the rate of air exchange rate for a room or hall of a given type.
For example, you need to know the parameters for a studio with a kitchen with a total volume of 20 m³. Take the minimum multiplicity for the kitchen - 6. It turns out that within 1 hour the air channels should move around L = 20 m³ * 6 = 120 m³.
It is also necessary to find out the cross-sectional area of the ducts installed in the ventilation system. It is calculated by the following formula:
S = πr2 = π / 4 * D2,
Where:
- S - cross-sectional area of the duct;
- π - the number "pi", a mathematical constant equal to 3.14;
- r - radius of the duct section;
- D - the diameter of the cross section of the duct.
Suppose that the diameter of the round duct is 400 mm, substitute it in the formula and get:
S = (3.14 * 0.4²) / 4 = 0.1256 m²
Knowing the cross-sectional area and flow rate, we can calculate the speed. The formula for calculating the air flow rate:
V = L / 3600 * S,
Where:
- V - air flow rate, (m / s);
- L - air consumption, (m³ / h);
- S - cross-sectional area of air channels (ducts), (m²).
Substituting the known values, we obtain: V = 120 / (3600 * 0.1256) = 0.265 m / s
Therefore, in order to provide the necessary air exchange rate (120 m3/ h) when using a round duct with a diameter of 400 mm, it will be necessary to install equipment to increase the air flow rate to 0.265 m / s.
It should be remembered that the previously described factors - parameters of the vibration level and noise level - directly depend on the speed of air movement.
If the noise exceeds the norm, you will have to reduce the speed, therefore, increase the cross section of the ducts. In some cases, it is enough to install pipes from another material or replace a curved channel fragment with a straight line.
Recommended air exchange rates
At the time of designing the building, each individual site is calculated. In production, these are workshops, in residential buildings - apartments, in a private house - floor blocks or separate rooms.
Before installing the ventilation system, it is known what are the routes and sizes of the main pipelines, what geometry the ventilation ducts are needed, and what pipe size is optimal.
Do not be surprised at the overall dimensions of the ducts in catering establishments or other institutions - they are designed to remove a large amount of used air
Calculations associated with the movement of air flows inside residential and industrial buildings are classified as the most complex, therefore, experienced qualified specialists are required to deal with them.
The recommended air speed in the ducts is indicated in SNiP - the regulatory state documentation, and when designing or commissioning objects they focus on it.
The table shows the parameters that should be followed when installing the ventilation system. Numbers indicate the speed of movement of air masses at the places of installation of channels and gratings in conventional units - m / s
It is believed that indoor air speed should not exceed 0.3 m / s.
Exceptions are temporary technical circumstances (for example, repair work, installation of construction equipment, etc.), during which the parameters can exceed the standards by a maximum of 30%.
In large premises (garages, production halls, warehouses, hangars), often instead of one ventilation system, there are two.
The load is divided in half, therefore, and the air speed is selected so that it provides 50% of the total estimated volume of air movement (removal of contaminated or clean supply).
When force majeure circumstances arise, there is a need for a sharp change in air speed or a complete suspension of the ventilation system.
For example, according to fire safety requirements, the air speed is reduced to a minimum in order to prevent the spread of fire and smoke in neighboring rooms during a fire.
To this end, cut-offs and valves are mounted in the ducts and in the transition sections.
Subtleties of choosing a duct
Knowing the results of aerodynamic calculations, you can correctly select the parameters of the ducts, or rather, the diameter of the round and the dimensions of rectangular sections. In addition, in parallel, you can select a forced air supply device (fan) and determine the pressure loss during the movement of air through the channel.
Knowing the amount of air flow and the value of its speed, you can determine what section of the air ducts are required.
To do this, take the formula inverse to the formula for calculating air flow:
S = L / 3600 * V.
Using the result, you can calculate the diameter:
D = 1000 * √ (4 * S / π),
Where:
- D - diameter of the cross section of the duct;
- S - cross-sectional area of air channels (ducts), (m²);
- π - the number "pi", a mathematical constant equal to 3.14 ;.
The resulting number is compared with factory standards allowed by GOST, and the products closest in diameter are selected.
If it is necessary to choose rectangular, rather than round ducts, then instead of the diameter, you should determine the length / width of the products.
When choosing, they are guided by an approximate section, using the principle a * b ≈ S and size tables provided by manufacturers. We remind you that according to the norms the ratio of width (b) and length (a) must not exceed 1 to 3.
Air ducts with a rectangular or square cross section are ergonomically shaped, which allows them to be installed close to the walls. This is used when equipping home hoods and masking pipes over ceiling mounted structures or over kitchen cabinets (mezzanines)
The generally accepted standards of rectangular channels: the minimum dimensions are 100 mm x 150 mm, the maximum dimensions are 2000 mm x 2000 mm. Round ducts are good in that they have less resistance, respectively, have minimal noise levels.
Recently, convenient, safe and lightweight plastic boxes have been specially manufactured for indoor use.
Useful videos will teach you how to work with physical quantities and help you better understand how the ventilation system works.
Video # 1.Calculation of natural ventilation parameters using a computer program:
Video # 2. Useful information about the ventilation system in a private house under construction:
The information in the article can be used for educational purposes and in order to better imagine the operation of the ventilation system.
For more accurate calculations of the air velocity when designing home communications, we recommend that you contact engineers who know the nuances of the ventilation device and help you choose the right duct sizes.
If you want to share personal experience gained with the installation of air ducts, interesting facts and specific information, please write comments in the block below. Ask questions about controversial issues. We or site visitors are happy to participate in the discussion.